Voltage in Parallel Calculator

Parallel branch currents, cable resistance and voltage drop, step by step
Find each branch current for 24 V across 12, 24 and 48 ohm in parallel
Find the resistance of a 30 m run of 2.5 mm^2 copper cable
Find the voltage drop for 16 A over a 30 m run of 2.5 mm^2 copper
Find the prospective fault current for a 0.76 ohm loop impedance on 230 V

Voltage Is Common, Current Divides

Two components are in parallel when both ends connect to the same pair of nodes. That is why the defining rule of a parallel circuit is about voltage:

V1=V2=тЛп=VsupplyItotal=I1+I2+тЛпV_1 = V_2 = \cdots = V_{\text{supply}} \qquad I_{\text{total}} = I_1 + I_2 + \cdots

Symbols and units: VV in volts (V), II in amperes (A), RR in ohms (╬й).

Each branch current is found independently from Ohm's law, In=V/RnI_n = V/R_n, and the equivalent resistance comes from summing conductances:

1Rp=1R1+1R2+тЛп\frac{1}{R_p} = \frac{1}{R_1} + \frac{1}{R_2} + \cdots

The result is always smaller than the smallest branch, because adding a path can only make it easier for current to flow.

The operating assumption: an ideal source that holds its voltage regardless of load, and wiring with no resistance of its own. Section two removes that second assumption, which is where most real-world errors live.

The mistake people make: adding parallel resistances. Adding is the series rule.

Real Cable Has Resistance

Once the wiring itself is included, the branches no longer share exactly the same voltage тАФ the cable steals some of it. A conductor's resistance is

R=╧БLAR = \frac{\rho L}{A}

with ╧Б\rho in ohm-metres (copper is 1.72├Ч10тИТ81.72 \times 10^{-8} ╬й┬╖m at 20 ┬░C), LL the conductor length in metres and AA the cross-sectional area in square metres. Note that 11 mm┬▓ =1├Ч10тИТ6= 1 \times 10^{-6} m┬▓.

For a two-core supply the current travels out and back, so the loop length is twice the route length:

Lloop=2├ЧLroute╬ФV=IRloopL_{\text{loop}} = 2 \times L_{\text{route}} \qquad \Delta V = I R_{\text{loop}}

The loop resistance also sets the prospective fault current, If=V/ZloopI_f = V / Z_{\text{loop}}, where ZloopZ_{\text{loop}} adds the supply's own impedance to the cable's.

These are teaching calculations. Conductor size, permissible voltage drop and disconnection time for a real installation are set by the applicable wiring code тАФ the NEC, BS 7671 or the local equivalent тАФ using its own tables, correction factors and design current. Never install to an arithmetic result alone.

Common Mistakes to Avoid

  • Adding resistances in parallel тАФ sum the reciprocals, then invert the sum once at the end.
  • Using the one-way length for a cable run тАФ the current goes and returns, so a 3030 m route is 6060 m of conductor.
  • Assuming every parallel branch really sees the source voltage тАФ with long cable runs it does not, and the far branch is starved.
  • Leaving the cross-section in mm┬▓ тАФ 2.52.5 mm┬▓ is 2.5├Ч10тИТ62.5 \times 10^{-6} m┬▓ in an SI formula.
  • Using the 20 ┬░C resistivity for a hot conductor тАФ a cable at 7070 ┬░C has roughly 20%20\% more resistance, which is precisely the condition voltage-drop checks care about.
  • Ignoring the source impedance in a fault calculation тАФ the transformer and the service cable are part of the loop.
  • Confusing conductor cross-section with cable diameter тАФ the overall sheath is much larger than the copper inside it.

Examples

Step 1: Every branch sees the full 2424 V, because they share both nodes
Step 2: I1=24┬аV├╖12┬а╬й=2.00┬аAI_1 = 24\ \text{V} \div 12\ \Omega = 2.00\ \text{A}
Step 3: I2=24┬аV├╖24┬а╬й=1.00┬аAI_2 = 24\ \text{V} \div 24\ \Omega = 1.00\ \text{A}
Step 4: I3=24┬аV├╖48┬а╬й=0.50┬аAI_3 = 24\ \text{V} \div 48\ \Omega = 0.50\ \text{A}
Step 5: Itotal=2.00+1.00+0.50=3.50┬аAI_{\text{total}} = 2.00 + 1.00 + 0.50 = 3.50\ \text{A}
Step 6: Rp=V/Itotal=24┬аV├╖3.50┬аA=6.86┬а╬йR_p = V/I_{\text{total}} = 24\ \text{V} \div 3.50\ \text{A} = 6.86\ \Omega
Step 7: Check by conductances: 1/12+1/24+1/48=7/481/12 + 1/24 + 1/48 = 7/48, so Rp=48/7=6.86┬а╬йR_p = 48/7 = 6.86\ \Omega, and it is smaller than the 12┬а╬й12\ \Omega branch
Answer: I1=2.00I_1 = 2.00 A, I2=1.00I_2 = 1.00 A, I3=0.50I_3 = 0.50 A, Itotal=3.50I_{\text{total}} = 3.50 A, RpтЙИ6.86R_p \approx 6.86 ╬й

Step 1: Loop length: L=2├Ч30┬аm=60┬аmL = 2 \times 30\ \text{m} = 60\ \text{m}
Step 2: Area: A=2.5┬аmm2=2.5├Ч10тИТ6┬аm2A = 2.5\ \text{mm}^2 = 2.5 \times 10^{-6}\ \text{m}^2
Step 3: R=╧БL/A=(1.72├Ч10тИТ8┬а╬йтЛЕm)(60┬аm)├╖(2.5├Ч10тИТ6┬аm2)R = \rho L/A = (1.72 \times 10^{-8}\ \Omega\cdot\text{m})(60\ \text{m}) \div (2.5 \times 10^{-6}\ \text{m}^2)
Step 4: Numerator: 1.032├Ч10тИТ6┬а╬йтЛЕm21.032 \times 10^{-6}\ \Omega\cdot\text{m}^2, so R=0.413┬а╬йR = 0.413\ \Omega
Step 5: ╬ФV=IR=(16┬аA)(0.413┬а╬й)=6.60┬аV\Delta V = IR = (16\ \text{A})(0.413\ \Omega) = 6.60\ \text{V}
Step 6: As a percentage: 6.60┬аV├╖230┬аV├Ч100=2.87%6.60\ \text{V} \div 230\ \text{V} \times 100 = 2.87\%
Step 7: Whether that is acceptable is decided by the applicable wiring code, not by this number
Answer: RloopтЙИ0.413R_{\text{loop}} \approx 0.413 ╬й, ╬ФVтЙИ6.60\Delta V \approx 6.60 V, about 2.9%2.9\% of 230230 V

Step 1: Zloop=Zexternal+Rcable=0.35┬а╬й+0.41┬а╬й=0.76┬а╬йZ_{\text{loop}} = Z_{\text{external}} + R_{\text{cable}} = 0.35\ \Omega + 0.41\ \Omega = 0.76\ \Omega
Step 2: If=V/Zloop=230┬аV├╖0.76┬а╬йI_f = V/Z_{\text{loop}} = 230\ \text{V} \div 0.76\ \Omega
Step 3: If=302.6┬аAI_f = 302.6\ \text{A}
Step 4: The protective device must clear this current within the disconnection time its own standard requires; that check uses the manufacturer's time-current curve, not this arithmetic
Answer: Zloop=0.76Z_{\text{loop}} = 0.76 ╬й, IfтЙИ303I_f \approx 303 A

Frequently Asked Questions

Yes, provided the connecting wiring has negligible resistance. Both ends of every branch meet at the same two nodes, so each branch sees the same potential difference. What differs is the current, which is largest in the smallest resistor.

Use R = rho L / A, with the resistivity in ohm-metres, the conductor length in metres and the cross-sectional area in square metres. For a two-core supply cable, use twice the route length because the current returns along the second core.

Find the loop resistance from R = rho L / A with the doubled length, then multiply by the design current: deltaV = IR. Compare it against the limit in the applicable wiring code, and correct the resistivity for the conductor's actual operating temperature.

Because each extra branch gives current another route. Conductances add, so the total conductance is larger than any one branch and its reciprocal, the resistance, is therefore smaller than any single branch.

Related Solvers

Try AI-Math for Free

Get step-by-step solutions to any math problem. Upload a photo or type your question.

Start Solving